Envirosafe’s 1,000 Gallon generator fuel system is designed specifically to supply generator or boilers. The Envirosafe generator fuel tank is fully compatible with a wide range of fuels. Our generator fuel tanks are available in either Flameshield (UL-142) or Fireguard (UL-2085) configurations and can be manufactured as a single tank or in split designs for the supply of two different fuel products. Each system we sell is built in our on-site manufacturing facility and is fabricated in accordance with The Steel Tank Institute’s specifications as well as meeting all UL standards. Envirosafe’s generator fuel system come as a ground fill with a lockable box or top fill options.
- Description
- Features
- Gallery
- Maintenance
- Accessories
Description
- Fireguard tanks insulate product in tank from ambient temperature variations, reducing
emissions to the environment - Available with dual compartments for multiple products in one tank with double bulk head to prevent cross contamination
- Primary and secondary tanks are tightness tested on site using standard air pressure test procedures
- Steel outer wall provides low cost maintenance and protection from weathering
- Primary storage tank and secondary containment are compatible with a wide range of fuels and chemicals
- Support designs available for all seismic requirements
- Interstitial space can be monitored for leak detection
- Available in self-contained double walled and protected double walled tanks
- Turn-key, inexpensive installation and startup
- 30 year tank warranty backed by the Steel Tank Institute
Features
1,000 Gallon Generator Fuel System Features
(1) UL-142 Flameshield or UL-2085 Fireguard Tank Mounted on Saddles
(2) 6” 8 Oz Emergency Vent Male w/O-ring
(1) 2” Stack Vent (12′ above grade) w/ 2” Mushroom Cap
(1) 7.5 Gal 4” Aluminum Overspill Container 179 Series hinged Style Fill Cap
(1) 818 Clock Gauge w/ Standard Float
(1) Engineered Hurricane Tie Down
(1) Interstitial Leak Gauge
(1) Tank Decal Kit
(1) Envirolastic 940 DTM Polyaspartic Urethane for High Performance Finish
(1) 1” Return Line Fitting Only
(1) Overfill Valve
(1) 1” Pickup with Drop Tube and Foot Valve 6” From Bottom of Line
(1) 18” Man way for easy inner tank accessibility
(1) UL Labeled & Listed (Per your local Fire Marshall)
(1) Step with Platform
STEEL THICKNESS 3/16” SHELL & 1/4” HEAD
(1) Touch-up Paint
Fireguard Benefits
UL 2080 Listed “Fire Resistant”
UL 2085 Listed “Protected”
Both Inner & Outer Steel Tanks built to UL Standards
Uniform Fire Code UFC “Protected” Tank
National Fire Protection (NFPA) 30 & 30A
International Fire Code (IFC)
Ballistics Protection
Impact protection
California Air Resources Board (CARB) for Air Emissions
Steel Tank Institute (STI) Standard F941 for Thermally Insulated Aboveground Storage Tanks
Flameshield Benefits
Tested Two-Hour Fire Resistance
Built to UL 142 Standards
Tested by Southwest Research Institute to SwRI 97-04
Double-Wall Tanks Have Fully Monitorable Interstitial Space for Leak detection
Gallery
1,000 Gallon Generator Fuel System Images
Maintenance
1,000 Gallon Generator Fuel System Maintenance
Accessories
1,000 Gallon Generator Fuel System Accessories
- Transfer System
- Polishing System
- Level Monitoring
- Catwalk
- Fuel Management
- Top Fill