5,000 Gallon Double Wall Tank

SKU: N/A
← All used tanks & equipmentSold 5,000 gallons nominal · UL 142 double wall
5,000 gallonsUsed listing · SoldAsk for a similar tank

USED LISTING / UL 142 DOUBLE-WALL TANKS

This listing has sold.

This listing has sold, but it stays visible as an example of what comes through the marketplace. Tell us the capacity, construction and delivery area you need and we’ll watch for a similar tank.

Status
Sold
Nominal capacity
5,000 gallons
Construction
UL 142 double-wall tanks
Operating fuel
4,500 gal at 90% operating / alarm
4,750 gal at 95% maximum / shutoff

PUBLISHED LISTING INFORMATION

Details as listed.

The description, photos and any prices below appear exactly as published for this listing.

  • Year Built: N/A
  • Size of Tank: 5,000 Gallons
  • Type of Tank: Double Wall Steel
  • UL Rating: UL-142
  • Any Issues (Leaks, etc.): Needs Paint
  • Dimensions: 11′ high x 96″ wide 14.8′ long

01 / BEFORE YOU BUY USED

Confirm the listing
before you plan the site.

A used tank arrives as listed. Condition, documents and equipment need confirming before delivery is scheduled.

01

Condition & documentation

Ask for the inspection notes, clear photos of the interior, interstice and fittings, and any tightness-test or inspection records that exist for this listing.

02

Construction & listing label

Check the nameplate or listing label against what your authority requires: fire-protected, double wall or single wall with separate containment.

03

Site & compliance

Plan setbacks, containment, venting and overfill devices for the intended site. A used tank arrives without the startup scope of a new system.

04

Delivery & installation

Confirm weight, dimensions, unloading, foundation and connection points. Ask about reconditioning or replacement equipment if the listing needs it.

02 / CAPACITY, DELIVERY & FUEL TURNOVER

Will your reorder reserve
last until delivery?

Choose capacity around your delivery quantity and the fuel you need while waiting for the truck. Then check that your consumption supports regular fuel turnover.

90% / OPERATING TARGET + ALARM4,500 gallons
95% / MAXIMUM + AUTO SHUTOFF4,750 gallons
100% / NOMINAL TANK VOLUME5,000 gallons

For aboveground atmospheric tanks, plan around 90% of nominal volume, with 95% as the maximum fill. For an equipped fuel system, the overfill alarm sounds at 90% and the overfill-prevention device stops additional fuel entering at 95%. A bare tank does not include these devices: specify the alarm and shutoff equipment separately. Keep normal operation at the 90% target. Confirm the supplied devices, settings and minimum fuel needed for pump drawdown.

THE BUYING ADVANTAGE

Plan for truckload pricing.

We use 7,500-gallon deliveries as the benchmark for the best wholesale rate per gallon. Confirm the supplier’s actual load size, delivered price and lead time for your location.

THE FUEL-QUALITY CHECK

Use fuel while it is fresh.

Divide the 4,500-gallon operating target by daily use to estimate the days of fuel on hand.

Review that turnover with your fuel supplier for your fuel, blend and storage conditions. Bigger storage only helps when the delivery reserve and fuel turnover both fit your operation.

03 / COMPARE WITH NEW

Weigh the listing against
a new package.

A used vessel can be the right call. So can a new tank with current documentation. Compare the scope before you commit.

YOUR NEXT STEP

Ask for a similar tank.

Tell us where the tank will go, what fuel it will hold and when you need it. We’ll confirm the details and delivery options.

Made in U.S.A. for over 30 years!

A Proud American Manufacturer for Over 30 YearsMADE IN U.S.A.

Contact Us

800-555-4754
info@envirosafetanks.com
1789 E CR 48, Bushnell, FL 33513

Headquarters, USA

1-800-555-4754