The Aboveground Storage Tank (AST) guidelines, developed in Vermont govern the design, as well as the positioning of an Aboveground OIl Tank. They give out inspection requirements and spill prevention for tank operators, as well as fuel suppliers. A law was passed in Vermont in 2016 requiring tanks to be removed during the conversion of natural gas.
The new standards must be imposed by July 1, 2017. All tanks must be inspected every three years. During the inspection, you might be required to bring the said tank to code if this wasn’t done.
There are several requirements for the installation of tanks that include: The vent line must terminate at the exterior of the building; tanks must gave a gauging device; vent alarm must terminate near the fill pipe; and so many more.
The installation of single-wall tanks are permitted but should have a thickness of at least 12 gauge. Double-walling of fiberglass tanks is recommended for outdoor use. Fiberglass tanks with single walls are accepted for indoor use. Skid tanks cannot be placed near a water supply.
The Petroleum Cleanup Fund (or PCF) gives assistance to residential owners in terms of the removal, replacement, or upgrade of USTs and Aboveground OIl Tank (ASTs). The fund grants owners with $2,000 for an indoor tank, $3,000 for an outdoor tank, and $4,000 for an underground tank.
An Aboveground OIl Tank must have a stable foundation, like a concrete pad, to prevent the tank from tipping over. All legs of the tank need to be in the same solid foundation. Blocks are prohibited. Reinforced concrete is highly recommended. A solid foundation is a requirement for flat bottom tanks. A tank on a flood plain must be anchored to the concrete pad.
Shelter is not required but highly recommended if the tank was placed at the gable end of the structure. If it is not placed at the gable end of the building, then shelter is required to protect it from the weather. However, no shelter is required for both tanks with secondary containment.
The tank installer must complete an inspection checklist and guidelines with the tank owner. According to regulations, fuel dealers must inspect the tank prior to delivery using the inspection checklist. Any problems discovered in the inspection must be corrected before fuel can be delivered.
If tanks are determined to be non-compliant and unsafe, the tank should be red-tagged by the fuel company. Red tagging a tank means that it does not comply and the dealer refuses to fill the tank due to possible environmental risks.
Fuel from an older tank cannot be transferred to a newer tank, unless the old tank is found to be in bad condition. If it will be transferred, the fuel must be pumped with a fuel conditioner and unused fuel must be disposed.
The tank must be removed if it is out-of-service for more than a year. All piping must be removed with it. No fill pipe must remain. The person responsible for removing the tank is also responsible for removing the fill pipes.
5 comments
Emily
July 12, 2019 at 2:03 pm
What are the regulations for AST’s and their distance from a building or parking lot? Do the rules differ by state or even municipality?
Lenny
July 16, 2019 at 9:06 am
What about the barriers in front of the tanks? The concrete pillars. How tall must they be, how deep into the ground, and the space between each one? Thank you for your time and help.
J Warriner
July 16, 2019 at 10:04 am
Yes they can differ by each state/municipality. Your best resource is your states DEP and Local Fire Marshall. Your local DEP has some info here: https://www.dep.pa.gov/Business/Land/Tanks/Aboveground-Storage-Tanks/Pages/default.aspx
J Warriner
July 16, 2019 at 10:07 am
Each states requirements may be different, you can locate your state DEP on our resources page under Above Ground Storage Tanks: State Requirements at: https://lkr.d3e.myftpupload.com/resources/
Steve Holt
July 17, 2019 at 11:32 am
Lenny,
In accordance with the National Fire Protection Association (NFPA) regarding collision protection for tanks storing flammable and combustible liquids:
NFPA 30A_4.3.7.2
1. They shall be constructed of steel not less than 4″ in diameter and shall be filled with concrete
2. They shall be spaced not more than 4′ on center
3. They shall be set not less than 3′ deep in concrete footing of not less than 15″ diameter
NFPA 30A_A.4.3.7.2
The top of the posts shall be set not less than 3′ above ground and should be located not less than 5′ from the tank.